  1.     SECTION 13980
  2.  
  3.     SPRINKLER PIPING COVER ASSEMBLIES
  4. NOTE ** The above section number and title may require revision if covering systems other than sprinkler piping.  Consult CSI MASTERFORMAT for numbers and titles applicable to use in project.
  5. NOTE ** Grice Engineering, Inc. fire sprinkler piping cover assembly.
  6. NOTE ** 
  7. NOTE ** This section is based on products manufactured by Grice Engineering, Inc., which is located at the following address:
  8. NOTE **     23 North Main Street
  9. NOTE **     P.O. Box 8037
  10. NOTE **     Janesville WI 53547-8037
  11. NOTE **     Tel:  (800) 800-3213
  12. NOTE **     Tel:  (608) 757-1335
  13. NOTE **     Fax:  (608) 757-1452
  14. NOTE ** 
  15. NOTE ** Grice Engineering, Inc. offers full design capability for sanitary, security, or decorative cover assemblies for new or existing:
  16. NOTE **     Fire sprinkler systems.
  17. NOTE **     Piping systems.
  18. NOTE **     Heating, ventilating, and air conditioning systems.
  19. NOTE **     Electrical systems.
  20. NOTE ** 
  21. NOTE ** SECTION 13980 - SPRINKLER PIPING COVER ASSEMBLIES, Copyright 1997, The Architect's Catalog, Inc.
  22.  
  23.  
  24. PART 1    GENERAL
  25.  
  26. 1.1    SECTION INCLUDES
  27. NOTE ** Delete any of the following paragraphs not applicable to project.
  28.  
  29.     A.    Cover Assemblies for Sprinkler Piping Systems.
  30.  
  31.     B.    Cover Assemblies for Plumbing Piping Systems.
  32.  
  33.     C.    Cover Assemblies for Heating, Ventilating, and Air Conditioning Systems.
  34.  
  35.     D.    Cover Assemblies for Electrical Conduit Systems.
  36.  
  37. 1.2    RELATED SECTIONS
  38. NOTE ** Delete any sections below not relevant to this project; add others as required.  Delete entire Article if specifying installation to cover existing systems.
  39.  
  40.     A.    Section 07900 - Joint Sealants.
  41.  
  42.     B.    Section 08710 - Door Hardware.
  43.  
  44.     C.    Section 13915 - Fire Protection Piping.
  45.  
  46.     D.    Sections of Division 15 affecting construction activities of this section.
  47.  
  48.     E.    Sections of Division 16 affecting construction activities of this section.
  49.  
  50. 1.3    REFERENCES
  51. NOTE ** Delete references from the list below that are not actually required by the text of the edited section.
  52.  
  53.     A.    ASTM A 366/A 366M - Standard Specification for Steel, Sheet, Carbon, Cold-Rolled, Commercial Quality.
  54.  
  55.     B.    ASTM A 653/A 653M - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process.
  56.  
  57.     C.    ASTM A 666 - Standard Specification for Austenitic Stainless Steel Sheet, Strip, Plate, and Flat Bar.
  58.  
  59. 1.4    SYSTEM DESCRIPTION
  60.  
  61.     A.    Design Requirements:
  62.         1.    Design complete cover assemblies to conceal components of the following systems in indicated areas:
  63. NOTE ** Delete any of the following systems that do not apply to project.
  64.             a.    Fire sprinkler systems.
  65.             b.    Piping systems.
  66.             c.    Heating, ventilating, and air conditioning systems.
  67.             d.    Electrical systems.
  68.         2.    Include all fittings to conceal systems completely, except for components indicated to be sight-exposed.
  69.         3.    Design cover assembly to be virtually non-removable using conventional tools after initial installation.
  70.  
  71. 1.5    SUBMITTALS
  72.  
  73.     A.    Submit under provisions of Section 01300.
  74.  
  75.     B.    Product Data:  Manufacturer's descriptive literature for specified system; include documentation of conformance to specified requirements.
  76.  
  77.     C.    Shop Drawings:
  78.         1.    Submit dimensioned scale drawings as follows:
  79.             a.    Plans:  Indicate locations of systems to be covered, and layout of each type cover assembly; include cover sizes and locations of joints and fittings.
  80.             b.    Details:  Indicate cross-section profile of each cover type; show each type fitting indicated on plans.
  81.         2.    Imprint shop drawings with seal and signature of professional mechanical engineer, employed by cover assembly manufacturer, licensed to practice in the State in which the project is located.
  82.  
  83.     D.    Selection Samples:
  84. NOTE ** Delete the following sub-paragraph if specifying custom colors or finishes, stainless steel finishes, or if colors and finishes are specified in this section.
  85.         1.    Cover:  Two sets of color chips representing manufacturer's full range of available colors.
  86.         2.    Joint Sealant:  Two sets of color samples representing manufacturer's full range of available colors.
  87.  
  88.     E.    Verification Samples:
  89.         1.    Cover:  Two samples, minimum size 12 inches (304 mm) long, representing actual color and finish of linear units.
  90.         2.    Joint Sealant:  Two samples, minimum size 12 inches (304 mm) long, representing actual sealant color.
  91.  
  92.     F.    Quality Assurance Submittals:
  93.         1.    Contractor's certification that:
  94.             a.    Cover assembly manufacturer meets specified qualifications.
  95.             b.    Installer's mechanics will have met specified qualifications before beginning construction activities of this section.
  96.         2.    Manufacturer's instructions:  Printed installation instructions for each assembly component, including storage requirements.
  97.  
  98.     G.    Closeout Submittals:
  99.         1.    Project record documents:  As-built drawings; two sets of specified shop drawings, with markings or notations indicating deviations between cover assemblies, as installed, and shop drawings.
  100.         2.    Manufacturer's recommendations for cleaning and maintaining finishes of sight-exposed components of assemblies.
  101.         3.    Warranty documents specified in WARRANTY Article of PART 1 of this section.
  102.  
  103. 1.6    QUALITY ASSURANCE
  104.  
  105.     A.    Qualifications:
  106.         1.    Manufacturer:  Minimum five (5) years documented experience producing cover assemblies similar to those specified in this section, having capability to design complete cover assemblies, employing training representative qualified to instruct installer's personnel in correct installation procedures, and employing professional mechanical engineer licensed to practice in the State in which the project is located.
  107.         2.    Installer:  Having mechanics who have successfully completed training conducted by manufacturer's training representative.
  108. NOTE ** Delete the following paragraph if not required.
  109.  
  110.     B.    Pre-Installation Meetings:
  111.         1.    Convene at job site seven (7) calendar days prior to scheduled beginning of construction activities of this section to review requirements of this section.
  112.         2.    Require attendance by representatives of the following:
  113.             a.    Installer of this section.
  114.             b.    Other entities directly affecting, or affected by, construction activities of this section.
  115.         3.    Notify Architect four (4) calendar days in advance of scheduled meeting date.
  116.  
  117. 1.7    DELIVERY, STORAGE, AND HANDLING
  118.  
  119.     A.    Store products of this section in manufacturer's unopened packaging until installation.
  120.  
  121.     B.    Maintain storage area conditions for products of this section in accordance with manufacturer's instructions until installation.
  122.  
  123. 1.8    PROJECT/SITE CONDITIONS
  124.  
  125.     A.    Field Measurements:  Take field measurements of areas to receive cover assemblies; note discrepancies on submitted shop drawings.
  126.  
  127. 1.9    WARRANTY
  128.  
  129.     A.    Manufacturer's Warranty:  Manufacturer's 10-year warranty against defects in products.
  130. NOTE ** Delete the following Article if maintenance stock not required.
  131.  
  132. 1.10    MAINTENANCE
  133.  
  134.     A.    Extra Materials:  For each assembly component, supply extra assembly components, in quantity equal to 5 percent of installed component.
  135.  
  136.  
  137. PART 2    PRODUCTS
  138.  
  139. 2.1    MANUFACTURERS
  140.  
  141.     A.    Acceptable Manufacturer:  Grice Engineering, Inc.; 23 North Main Street, P.O. Box 8037, Janesville WI 53547-8037; ASD. Tel. (800) 800-3213 or (608) 757-1335, Fax. (608) 757-1452.
  142. NOTE ** Delete one of the two following paragraphs; coordinate with Division 1 requirements.
  143.  
  144.     B.    Requests for substitution will be considered in accordance with provisions of Section 01600.
  145.  
  146.     C.    Substitutions:  Not permitted.
  147.  
  148.     D.    Unless otherwise specified for an individual product or material, supply all products specified in this section from the same manufacturer.
  149.  
  150. 2.2    COMPONENTS
  151.  
  152.     A.    Linear Units:  Factory-formed profiles indicated on shop drawings, minimum length 5 feet (1524 mm), with horizontal edges formed to continuous profile designed to interlock with mounting clips and to provide sealant groove.
  153. NOTE ** Retain one of the following three sub-paragraphs to specify material.
  154.         1.    Material:  Stainless steel sheet conforming to ASTM A 666, Type 304.
  155.         2.    Material:  Cold-rolled commercial quality steel sheet conforming to ASTM A 366/A 366M.
  156.         3.    Material:  Galvanized lock-forming quality steel sheet conforming to ASTM A 653/A 653M, G90 (Z275) coating.
  157. NOTE ** Retain one of the following five sub-paragraphs to specify material.
  158.         4.    Sheet thickness:  16 gage (1.52 mm).
  159.         5.    Sheet thickness:  18 gage (1.22 mm).
  160.         6.    Sheet thickness:  20 gage (0.91 mm).
  161.         7.    Sheet thickness:  22 gage (0.76 mm).
  162.         8.    Sheet thickness:  24 gage (0.61 mm).
  163. NOTE ** Delete the following sub-paragraph if not required.
  164.         9.    Perforations:  Factory-punched before finishing of metal; locations and patterns indicated on shop drawings.
  165. NOTE ** Retain one of the following eight sub-paragraphs to specify finish.
  166.         10.    Finish:  Number 4 satin polish.
  167.         11.    Finish:  Galvanized finish for enhanced adhesion of field-applied finishes.
  168.         12.    Finish:  Baked enamel, white color.
  169.         13.    Finish:  Baked enamel, off-white color.
  170.         14.    Finish:  Baked enamel, custom color matching Architect's sample.
  171.         15.    Finish:  Baked fluoropolymer enamel, _________ color.
  172.         16.    Finish:  Baked fluoropolymer enamel, color to be selected from manufacturer's full range of available colors.
  173.         17.    Finish:  Baked fluoropolymer enamel, custom color matching Architect's sample.
  174.  
  175.     B.    Fittings:  Supply fittings indicated on shop drawings, including, but not limited to, the following:
  176.         1.    Exterior and interior corner units:  Same material, sheet thickness, and finish as linear units, factory-fabricated profile matching linear units; field-formed or shop-formed units not permitted.
  177.         2.    End caps:  Same material, sheet thickness, and finish as linear units, factory-fabricated profile matching linear units; field-formed or shop-formed units not permitted.
  178.         3.    Anchor clips:  Spring steel, zinc-plated, minimum 250 pounds (113.25 kg) uplift resistance at free end, formed to interlock with horizontal edges of linear units, with fastener types and sizes recommended by manufacturer for indicated substrates.
  179. NOTE ** Delete the following sub-paragraph if specifying institutional assembly with overlapping butt joints.
  180.         4.    Internal splicing sleeves:  Formed to fit inside linear units, of material compatible with linear unit material.
  181.         5.    Fire sprinkler head spacers.
  182. NOTE ** Since, after installation, the cover assembly is virtually non-removable with conventional tools, there are two methods for accessing concealed piping elements which require servicing:
  183. NOTE ** 
  184. NOTE ** Placing access doors at service points.
  185. NOTE ** Using cover removal tool at cover sections where access is required.
  186. NOTE ** 
  187. NOTE ** Use of cover removal tool may require replacement of anchor clips at locations of cover removal, and will require re-application of sealant at those locations; the manufacturer recommends that access doors be placed at locations which may require moderate-to-frequent service.
  188. NOTE ** 
  189. NOTE ** Retain one or both of the following sub-paragraphs as applicable to project.
  190.         6.    Access doors and frames:
  191.             a.    Fabricated of same material, sheet thickness, and finish as linear units.
  192.             b.    Provide each door with latching assembly.
  193.             c.    Provide each door with latching assembly, lock cylinder, and two keys; key all access door locks alike.
  194.             d.    Provide each door with latching assembly to accept cylinder specified in Section 08710.
  195.         7.    Cover removal tool:  Supply five (5) units to Owner.
  196. NOTE ** Retain one of the following two paragraphs to specify joint sealant.
  197.     C.    Joint Sealant:  Specified in Section 07900.
  198.  
  199.     D.    Joint Sealant:
  200.         1.    Acceptable product:  One of the following:
  201. NOTE ** Review the following list; sanitary or other requirements may dictate that  one or more of the listed products be deleted.
  202.             a.    Sikadur(R) 51 two-part epoxy sealant.
  203.             b.    Sikaflex(R) TR two-part epoxy sealant.
  204.             c.    Sonneborn Ultra polyurethane sealant.
  205. NOTE ** Retain one of the following sub-paragraphs to specify color selection.
  206.         2.    Color:  _______________.
  207.         3.    Color:  To be selected from sealant manufacturer's full range of available colors.
  208. NOTE ** Retain one of the following paragraphs for cover installation over new piping, as applicable to project; delete both if cover installation is over existing piping.
  209.  
  210.     E.    Pipe Support Devices:  Specified in Section 15145.
  211.  
  212.     F.    Pipe Support Devices:  NFPA-tested and certified for indicated use, UL-listed, including, but not limited to, the following:
  213.         1.    Low-profile steel hanger for supporting steel pipe and CPVC pipe.
  214.         2.    Low-profile copper-coated hanger for supporting copper pipe or tubing.
  215.  
  216.  
  217. PART 3    EXECUTION
  218.  
  219. 3.1    EXAMINATION
  220.  
  221.     A.    Verification of Conditions:  Systems to be concealed are located and grouped in accordance with shop drawings.
  222.  
  223.     B.    Installer's Examination:
  224.         1.    Have installer of this section examine conditions under which construction activities of this section are to be performed, then submit written notification if such conditions are unacceptable.
  225.         2.    Transmit two copies of installer's report to Architect within 24 hours of receipt.
  226.         3.    Beginning construction activities of this section before unacceptable conditions have been corrected is prohibited.
  227.         4.    Beginning construction activities of this section indicates installer's acceptance of conditions.
  228.  
  229. 3.2    INSTALLATION
  230.  
  231.     A.    Field Cutting:
  232. NOTE ** Delete any of the following sub-paragraphs that do not apply to project: third sub-paragraph applies to painted finishes only.
  233.         1.    Field cut linear units for required fit at ends of runs; make cuts square for hairline end-to-end butt joints.
  234.         2.    Field cut openings for indicated sprinkler heads
  235.         3.    Apply touch-up paint matching finish of linear units at cut openings.
  236.  
  237.     B.    Install components in accordance with shop drawings and manufacturer's instructions.
  238. NOTE ** Retain the following paragraph if specifying security cover installation; delete if not applicable to project.
  239.  
  240.     C.    Overlap ends of linear units minimum 1 inch (25 mm) at end-to-end joints; place rivets at intervals of 1.25 inches (31 mm), maximum, spaced 0.50 inches (12 mm), maximum from end of overlapping section.
  241.  
  242.     D.    Apply specified sealant in accordance with requirements of Section 07900 and instructions of sealant and cover assembly manufacturers.
  243.  
  244.     E.    Site Tolerances:  Maximum variation of cover assembly from plumb or level; 1/4 inch in 10 feet (6.3 mm in 3 m), non-cumulative.
  245.  
  246. 3.3    PROTECTION
  247.  
  248.     A.    Protect installed products of this section from damage to function or finish by subsequent construction activities.
  249.  
  250.     B.    Repair minor damage to finishes in accordance with manufacturer' recommendations.
  251.  
  252.     C.    Replace products having damage to function, and products having damage to finishes which cannot be repaired to Architect's acceptance.